⚡ Transformer MCQs for PSU Exams Part 2⚡
⚡ Transformer Quiz – Part 2 (Q13–20) ⚡
๐ This is Part 2 of the transformer quiz. It covers saturation, phasor diagrams, tests, equivalent circuits, and voltage regulation. Complete this section to finish the full set!
13Can a 50 Hz transformer be used at 25 Hz with rated voltage? ๐
Check Answer
Answer: b) No, flux doubles → saturation
Explanation: Flux ∝ V/f. At half frequency, flux doubles → core saturation.
Explanation: Flux ∝ V/f. At half frequency, flux doubles → core saturation.
14On load phasor diagram of transformer, the core loss component of current remains in phase with? ๐
Check Answer
Answer: b) Primary supply voltage
Explanation: Core loss current represents real power → in phase with supply voltage.
Explanation: Core loss current represents real power → in phase with supply voltage.
15The induced reactance of a transformer depends on? ๐
Check Answer
Answer: d) Leakage flux
Explanation: Leakage reactance arises from leakage flux linking only one winding.
Explanation: Leakage reactance arises from leakage flux linking only one winding.
16Open circuit test performed on a transformer with? ๐งช
Check Answer
Answer: a) Rated secondary terminal voltage
Explanation: Conducted at rated voltage on LV side with secondary open to measure core losses.
Explanation: Conducted at rated voltage on LV side with secondary open to measure core losses.
17In transformer equivalent circuit, the core losses are represented as? ๐
Check Answer
Answer: b) Shunt resistance
Explanation: Core losses are modeled as a resistance in parallel with magnetizing branch.
Explanation: Core losses are modeled as a resistance in parallel with magnetizing branch.
18When a transformer is operating on no load, the primary applied voltage is approximately balanced by? ⚡
Check Answer
Answer: a) Primary induced emf
Explanation: Applied voltage ≈ induced emf in primary, since drops are negligible.
Explanation: Applied voltage ≈ induced emf in primary, since drops are negligible.
19Full load voltage regulation of a power transformer is zero when power factor of the load is near? ๐
Check Answer
Answer: a) Unity and lagging
Explanation: At unity PF, voltage drop due to reactance cancels → regulation zero.
Explanation: At unity PF, voltage drop due to reactance cancels → regulation zero.
20In transformer, zero voltage regulation at full load is? ๐
Check Answer
Answer: b) Possible at leading power factor load
Explanation: Leading PF load can cause terminal voltage rise, making regulation zero or negative.
Explanation: Leading PF load can cause terminal voltage rise, making regulation zero or negative.